|
Owner's Manual
Models 6050 and 6100
Vehicular Swing Gate Operators
Table of Contents
|
Use this manual with the following models only.
Models 6050-080, 6050-081, 6100-080, 6100-081, 6100-082, 6100-083 with
4502-010 circuit board.
NOTE: Models 6100-082 and 6100-083 will have a supplemental manual (P/N
2340-065) that describes the operation and setup of the optional battery
backup system available with these units, and provides additional wiring
information for these units.
DoorKing, Inc. reserves the right to make changes in the products described
in this manual without notice and without obligation of DoorKing, Inc. to
notify any persons of any such revisions or changes. Additionally, DoorKing,
Inc. makes no representations or warranties with respect to this manual.
This manual is copyrighted, all rights reserved. No portion of this manual
may be copied, reproduced, translated, or reduced to any electronic medium
without prior written consent from DoorKing, Inc.
|
IMPORTANT NOTICES
Vehicular gate systems provide convenience to their users and limit
vehicular traff ic onto your property. These systems can produce high levels
of force; therefore it is important that you are aware of possible hazards
associated with your gate operating system. These hazards may include pinch
points, entrapment, absence of controlled pedestrian access or traffic
backup.
Be sure that the installer has instructed you on the proper operation of the
gate and gate operator system. Be sure that the installer has trained you
about the basic functions of the reversing systems associated with your gate
operating system and how to test them. These include reversing loops,
inherent reversing system, and may include electric edges, photoelectric
cells, or other external devices.
• This Owner's Manual is your property. Keep it in a safe place for future
reference.
• Loops and loop detectors, photo-cells or other equivalent devices must be
installed with this gate operator to prevent the gate from closing on
vehicular traffic.
• The speed limit for vehicular traff ic through the gate area is 5 MPH.
Install speed bumps and signs to keep vehicular traffic from speeding
through the gate area. Failure to adhere to posted speed limits can result
in damage to the gate, gate operator, and to the vehicle.
• Be sure that all residents are familiar with the proper use of the gate
and gate operator. Be sure that all residents are familiar with the possible
hazards associated with the gate system.
• Be sure that all warning signs are permanently installed on both sides of
the gate in an area where they are fully visible to traffic.
• It is your responsibility to periodically check all reversing devices. If
any of these devices are observed to function improperly, remove the
operator from service immediately and contact your installing or servicing
dealer.
• Follow the recommended maintenance schedule.
• Do not allow children to play in the area of the operator or to play with
any gate-operating device.
• Be sure that all activating devices are installed a minimum distance of 10
feet away from the gate and gate operator, or in such a way that a person
cannot touch the gate or gate operator while using the activating device. If
activating devices are installed in violation of these restrictions,
immediately remove the gate operator from service and contact your
installing dealer.
• To remove the gate operator from service, operate the gate to the full
open position and then shut off power to the operator at the service panel.
|
 |
|

|
IMPORTANT SAFETY INSTRUCTIONS
WARNING - To reduce the risk of injury or death:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. Never let children operate or play with gate controls. Keep the remote
control away from children.
3. Always keep people and objects away from gate. NO ONE SHOULD CROSS THE
PATH OF THE MOVING GATE.
4. Test the operator monthly. The gate MUST reverse on contact with a rigid
object or stop or reverse when an object activates the non-contact sensors.
After adjusting the force or the limit of travel, retest the gate operator.
Failure to adjust and retest the gate operator properly can increase the
risk of injury or death.
5. KEEP GATES PROPERLY MAINTAINED. Read the owner's manual. Have a qualified
service person make repairs to gate hardware.
6. The entrance is for vehicles only. Pedestrians must use separate
entrance.
7. SAVE THESE INSTRUCTIONS!
|
RESTRICTIONS AND WARNINGS
Install The Gate Operator Only If.
The operator is appropriate for the usage Class of the application.
All exposed pinch points are eliminated or guarded.
This operator is intended for installation only on swing gates used to
control vehicular traffic. Pedestrians must be provided with a separate
access opening.
The gate must be installed in a location so that sufficient clearance is
provided between the gate and adjacent structures when opening and closing
to reduce the risk of entrapment (see diagram). Swinging gates should not
open into public access areas.
The gate must be properly installed and work freely in both directions prior
to the installation of the gate operator. Do not over-tighten the operator
clutch to compensate for a damaged gate.
Controls must be far enough from the gate so that the user is prevented from
coming in contact with the gate while operating the controls. Outdoor or
easily accessible controls should have a security feature to prevent
unauthorized use.
All warning signs and placards must be installed where visible in the area
of the gate.
|
 |
 |
|

|
ENTRAPMENT PROTECTION
This vehicular gate operator is equipped with an inherent adjustable clutch
(Type C - Primary) and an inherent (Type A - Secondary) entrapment sensing
system. This system will sense an obstruction in both the opening and
closing gate cycles, and will cause the gate to reverse direction should an
obstruction be encountered. If the system detects a second obstruction
before reaching the full open or close limit after the initial reversal, an
alarm will activate and the operator will require a reset before resuming
normal operation. See Section 4 for more information.
EXTERNAL ENTRAPMENT PROTECTION
Non-contact and contact sensors must be installed individually or in
combination with each other to provide external entrapment protection. For
gate operators utilizing a non-contact sensor:
• See diagram below for placement of non-contact sensors.
• Care should be exercised to reduce the risk of nuisance tripping, such as
when a vehicle trips the sensor while the gate is still moving, and
• One or more non-contact sensors shall be located where the risk of
entrapment or obstruction exists, such as the perimeter reachable by a
moving gate or barrier.
|
 |
For gate operators utilizing a contact sensor:
A hardwired contact sensor shall be located and its wiring arranged so that
the communication between the sensor and the gate operator is not subjected
to mechanical damage.
A wireless contact sensor such as one that transmits radio frequency (RF)
signals to the gate operator for entrapment protection functions shall be
located where the transmission of the signals are not obstructed or impeded
by building structures, natural landscaping or similar obstruction. A
wireless contact sensor shall function under the intended end-use
conditions.
|
|

|
GLOSSARY
GATE - A moving barrier such as a swinging, sliding, raising, lowering, or
the like, barrier, that is a stand-alone passage barrier or is that portion
of a wall or fence system that controls entrance and/or egress by persons or
vehicles and completes the perimeter of a defined area.
RESIDENTIAL VEHICULAR GATE OPERATOR-CLASS I - A vehicular gate operator (or
system) intended for use in a home of one-to four single family dwelling, or
garage or parking area associated therewith.
COMMERCIAL / GENERAL ACCESS VEHICULAR GATE OPERATOR-CLASS 11 - A vehicular
gate operator (or system) intended for use in a commercial location or
building such as a mufti-family housing unit (five or more single family
units), hotels, garages, retail store, or other building servicing the
general public.
INDUSTRIAL / LIMITED ACCESS VEHICULAR GATE OPERATOR-CLASS III - A vehicular
gate operator (or system) intended for use in an industrial location or
building such as a factory or loading dock area or other locations not
intended to service the general public.
RESTRICTED ACCESS VEHICULAR GATE OPERATOR-CLASS IV - A vehicular gate
operator (or system) intended for use in a guarded industrial location or
building such as an airport security area or other restricted access
locations not servicing the general public, in which unauthorized access is
prevented via supervision by security personnel.
SYSTEM -.In the context of these. requirements, a system refers to a group
of interacting devices intended to perform a common function.
WIRED CONTROL - A control implemented in a form of fixed physical
interconnections between the control, the associated devices, and an
operator to perform predetermined functions in response to input signals.
WIRELESS CONTROL - A control implemented in means other than fixed physical
interconnections (such as radio waves or infrared beams) between the
control, the associated devices, and an operator to perform predetermined
functions in response to input signals.
INHERENT ENTRAPMENT SENSOR SYSTEM - An automatic sensor system which senses
entrapment of a solid object and is incorporated as a permanent and integral
part of the operator.
ENTRAPMENT - The condition when an object is caught or held in a position
that increases the risk of injury.
|
|

|
TABLE OF CONTENTS
Section 1 - Installation
1.1 Specifications
1.2 Mounting Post / Base Plate Installation
1.2.1 Post Mount Operator
1.2.2 Pad Mount Operator
1.3 Mounting the Operator
1.3.1 Post Mounted Operators
1.3.2 Pad Mounted Operators
1.4 Arm Assembly and Installation
1.4.1 Crank Ann Assembly
1.4.2 Connecting Arm
1.4.3 Test the Installation
1.5 Warning Sign Installation
1.6 Setup for Gates Opening Other Than 90 deg
1.6.1 Determine the Location of the Operator
1.6.2 Arm Length Calculations
Section 2 - Wiring
Conduits
2.1 High Voltage Connections
2.1.1 Single Operator
2.1.2 Master / Slave Operators
2.2 Control Wiring
2.2.1 Radio Receiver Wiring
2.2.2 Secondary Entrapment Protection Device Wiring
2.3 Loop Detector Wiring
2.4 Magnetic Lock Wiring
2.4.1 Direct Power
2.4.2 Indirect Power
2.5 Gate Tracker Connections
2.6 Auxiliary Devices
2.6.1 Alarm Reset Switch
2.6.2 Auxiliary Stop Switch
2.7 Main Terminal Identification and Description
2.8 Auxiliary Terminal Identification and Description
Section 3 - Adjustments
3.1 Circuit Board Adjustments
3.2 Switch Settings
3.2.1 SW I (Top Switch) Description and Function
3.2.2 SW 2 (Bottom Switch) Description and Function
3.3 Limit Adjustment
3.4 Entrapment Sensing System
3.4.1 Clutch Adjustment
3.4.2 Secondary Entrapment Protection System
Section 4 - Operating Instructions
4.1 Power and Reset Switches
4.2 Shutdown Conditions
4.2.1 Soft Shutdown
4.2.2 Resetting a Soft Shutdown
4.2.3 Hard Shutdown
4.2.4 Resetting a Hard Shutdown
4.3 Manual / Emergency Gate Operation
4.3.1 Emergency Vehicle Access Conditions
4.3.2 Fail-Safe Manual Operation
4.3.3 Manual Release
Section 5 - Maintenance and Troubleshooting
5.1 Maintenance Schedule
5.2 Trouble Shooting
5.3 Accessories
Wire Diagram Model 6050 / 6100
Wire Diagram Model 6100 with Battery Backup
Illustrated Parts Breakdown Model 6050
Illustrated Parts Breakdown Model 6100
Illustrated Parts Breakdown Model 6100 with Battery Backup
|
|

|
SECTION 1 - INSTALLATION
Prior to beginning the installation of the swing gate operator, we suggest
that you become familiar with the instructions, illustrations, and wiring
guide-lines in this manual. This will help insure that your installation is
performed in an efficient and professional manner.
The proper installation of the vehicular swing gate operator is an extremely
important and integral part of the overall access control system. Check all
local building ordinances and building codes prior to installing this
operator. Be sure your installation is in compliance with local codes.
1.1 SPECIFICATIONS
|
| Class of Operation: |
Model 6050 - Class I only, Model 6100 - Class 1, 11,
111, IV |
| Type of Gate: |
Vehicular Swing Gates Only |
| Horsepower: |
Model 6050 - 1/3 H.P., Model 6100 - 1/2 H.P. |
| Voltage / Phase: |
115 VAC Single-phase only |
| Current: |
Model 6050 - 4.3 amps, Model 6100 - 5.4 amps |
| Max Gate Weight: |
Model 6050 - 400 Lbs., Model 6100 - 500 Lbs. |
| Max Gate Length: |
Model 6050 - 10 Ft., Model 6100 - 14 Ft. |
| Cycles / Hr: |
Model 6050 - 1 O/Hr, Model 6100 - 60/Hr |
| Speed: |
900 in approximately 12 seconds |
| Entrapment Protection: |
Primary - Inherent adjustable clutch (Type C)
Secondary - Inherent entrapment sensing system (Type A)
and provision for connection of a non-contact sensor (Type
B1) |
|
| |
|

|
1.2 MOUNTING POST / BASE
PLATE INSTALLATION
1.2.1 POST MOUNT OPERATOR
|
| X |
Y |
GATE WIDTH |
| 34 |
30.75 |
14 FT. |
| 30 |
26.50 |
12 FT. |
| 26 |
22.25 |
10 FT. |
|
|
1. Screw the two mounting pipes supplied into
the operator mounting plate.
2. Using Table 1 and Figure 2 determine where POINT C on the mounting plate
/ pipe assembly needs to be located. The location of this assembly and the Y
measurement is dependent on the X measurement that you choose.
3. X is the measurement from the center of the gate hinge to the center of
the gate bracket and defines the position of the All and A2 points.
4. Once the location of POINT C has been determined, construct a form for
the concrete pad according to Figure 3 and place the assembly into the form.
Note that
the depth of the pad is determined by soil conditions and local building
codes.
5. Determine the height of the assembly required for your installation.
Refer to Figure 4.6. IMPORTANT!! Prior to pouring concrete to anchor the
mounting plate / pipe assembly, be sure that POINT C is located correctly
and that the mounting plate is level and at the correct height. Conduits can
be run into the pad as required.
7. Let the concrete cure for 48 hours before proceeding with the
installation of the gate operator.
|
 |
|

|
 |
The concrete pad is sized so that there is a
minimum of four (4) inches of concrete from the outside edge of the mounting
pipes.
The height requirement is determined by adjusting the mounting plate / pipe
assembly so that the top of the mounting plate is 4 3/4 inches above the top
of the gate rail (Figure 4). This will allow you to mount the gate bracket
onto the bottom rail of the gate and will keep the crank and connecting arms
level (see page 8, Figure 12).
The top of the mounting plate must be at least six (6) inches above the
ground. If it is less than this, the gate arms will scrape the ground when
the operator starts.
It is very important that the operator mounting plate is level.
|
 |
|

|
1.2.2 PAD MOUNT OPERATOR
|
| X |
Y |
Gate Width |
| 34 |
32 |
14 FT |
| 30 |
28 |
12 FT |
| 26 |
24 |
10 FT |
|
|
| |
1. Using Table 2 and Figure 5 determine the
location of the concrete pad and mounting plate. The location of the pad and
base plate and the Y measurement is dependent on the X measurement that you
choose.
2. X is the measurement from the center of the gate hinge to the center of
the gate bracket and defines the position of the Al and A2 points.
3. Once the location of the pad and base plate has been determined,
construct a form for the concrete pad according to Figure 6. Note that the
depth of the pad is determined by soil conditions and local building codes.
The pad is sized so that there is four (4) inches of concrete around the
mounting plate when it is installed on the pad.
4. IMPORTANT!! Be sure that the top of the pad is level.
5. Let the concrete cure for 48 hours before proceeding with the
installation of the gate operator.
6. Anchor the concrete mounting plate to the pad using eight (8) 3/8 x 3
sleeve anchors (not supplied). It is important that the concrete base plate
is located correctly on the
pad so that the A1-A2 line will intersect the operator output shaft as shown
in Figure
5.
|
 |
|

|
The concrete pad is sized so that there is a
minimum of four (4) inches of concrete around the perimeter of the pad.
Attach the gate bracket to the gate so that the top of the mounting plate is
4 3/4 inches above the top of the gate bracket as shown in Figure 7. This
will keep the crank and connecting arms level (see page 8, Figure 12).
|
 |
The height requirement can also be ascertain by
placing the gate bracket so that it is 5 3/4 inches (10 1/2 - 4 3/4) above
the bottom of the base plate, or above the top of the concrete pad.
The position of the gate bracket on the gate is directly related to the
height of the concrete pad above ground level. If allowed by local codes,
the top of the concrete pad can be flush with ground level as shown in
Figure 7, which will allow the gate bracket to be lower on the gate.
|
 |
|

|
1.3 MOUNTING THE OPERATOR
1 . Remove the operator from the shipping carton.
2. Remove the cover from the operator.
3. It is advisable to remove the conduit knockouts (as required) prior to
mounting the operator onto the operator base plate.
1.3.1 POST MOUNTED OPERATORS
1 Bolt the operator to the mounting plate using four (4) 3/8-16 x 3/4 bolts
supplied.
These bolts secure the operator to the mounting plate at the locations that
have nut
plates (Figure 9).
2. Use the remaining hardware, three (2) 3/8-16 x 1 1/4 bolts, three (2) 3/8
washers,
and three (2) 3/8-16 nuts to secure the operator to the mounting plate at
the three
locations without nut plates.
3. Route conduits into the operator at this time.
|
 |
 |
|

|
1.3.2 PAD MOUNTED
OPERATORS
1. Place the operator on the mounting plate so that the four (4) mounting
holes are in
alignment and the output shaft extends in front of the mount plate base
(Figure 10).
2. Bolt the operator to the mounting plate using two (2) 3/8-16 x 1 bolts,
two (2) 3/8
washers, and two (2) 3/8-16 nuts in the holes marked A (Figure 11).
3. Use the remaining hardware, two (2) 3/8-16 x 1 1/4 bolts, two (2) 3/8
washers, and
two (2) 3/8-16 nuts in the holes marked B (Figure 11).
4. Use the three (3) 5/16 lock nuts to secure the bolts from the bottom of
the operator
base to the mount plate base. These bolts are labeled "Bolt" in Figure 11.
5. Route conduits into the operator at this time.
|
 |
 |
|

|
1.4 ARM ASSEMBLY AND
INSTALLATION
|
 |
1.4.1 CRANK ARM ASSEMBLY
1. Attach the crank arm and crank power arm to the operator output shaft
using the supplied hardware (Figure 13). Position the arm so that it is
pointing towards the gate.
2. Do not insert the lock pin or lock into the crank arm assembly at this
time. It will be installed later.
3. Adjust the lock nut so that it is snug against the washer, but will still
allow the crank power arm to turn with little force.
|
 |
|

|
 |
4. Slide the connector assembly (Figure 14)
onto the crank arm so that the flange is away from the gate.
5. The connector assembly must be positioned on the crank arm at the correct
distance from the operator shaft to allow the gate to open a full 909. To
determine this measurement, refer back to SECTION 1.2. Measure the distance
from POINT Al to POINT A2 then divide this measurement by 2. The result is
the crank arm assembly length. (Table 3 determines this measurement for the
three different X measurements provided in SECTION 1.2.)
|
| X |
Crank Arm |
| 34 |
24.04 |
| 30 |
21.21 |
| 26 |
18.38 |
|
|
| |
6. Adjust the connector assembly on the crank
arm so that the distance from the center of the operator output shaft to the
center of the pivot on the connector assembly is equal to the result of the
computation in step 4 above then tighten the setscrews to secure the
connector in place.
7. The length of the crank arm / connector assembly is dependent on the X
measurement that was selected in SECTION 1.2. This length can be calculated
by using the Pythagorean Theorem A2 + B2 = C2
to find the hypotenuse (Al, A2) of the right triangle formed by the gate
hinge point, point Al and point A2. Once the hypotenuse is found, divide it
by 2 to get the required crank arm / connector assembly length. The crank
arm lengths in Table 3 where determined by this method.
1.4.2 CONNECTING ARM
1. Place the gate in the full closed position.2. Once the crank arm
assembly length is set, slide one end of the connector arm through the
connector assembly and attach the other end to the gate bracket as shown in
Figure 15. Attach the arm to the bottom side of the gate bracket.
3. Be sure that the gate is fully closed and then tighten the three
setscrews in the connector assembly to lock the connecting arm in place.
|
 |
|

|
1.4.3 TEST YOUR
INSTALLATION
• When the gate is fully closed, the drive and connecting arms should be in
a straight line as shown in Figure 16.
• Manually open the gate. The connecting arm should rotate beneath the drive
arm and output shaft. When the gate is fully open, the drive arm should be
directly over the connecting arm as shown in Figure 17.
• If the gate does not open a full 900, this means that the drive arm is
less than half the A1-A2 measurement. Re-check this measurement and reset
the drive arm length.
• If the gate opens farther than 900, this means that the drive arm is
greater than half the A1-A2 measurement. Re-check this measurement and reset
the drive arm length.
• Shortening the crank arm 1" will stop the gate 2" short. Lengthening the
crank arm 1" will cause the gate to swing 2 inches farther.
• Once you are sure that the gate opens and closes fully, trim the excess
length off of the drive and connecting arms.
|
 |
1.5 WARNING SIGN
INSTALLATION
This DoorKing Swing Gate Operator is shipped with two warning signs. The
purpose of the warning sign is to alert uninformed persons, and to remind
persons familiar with the gate system, that a possible hazard exist so that
appropriate action can be taken to avoid the hazard or to reduce exposure to
the hazard.
• Permanently install the supplied warning signs in locations so that the
signs are visible by persons on both sides of the gate.
• Use appropriate hardware such as wood or sheet metal screws (not supplied)
to install the warning signs.
|
|

|
1.6 SETUP FOR GATES
OPENING OTHER THAN 900
|
 |
1.6.1 DETERMINE THE
LOCATION OF THE OPERATOR
1. Determine where the gate-bracket will be attached to the gate. If the
gate will be opened greater than 900, the gate bracket should be mounted no
farther than 30 inches from the center of the hinge point.
2. Once the gate bracket has been attached to the gate, close the gate fully
and mark a
point on the ground directly under the center of the mounting bracket. Label
this point Al (Figure 19).
|
 |
3. Swing the gate to the desired open position.
This can be less than 900, 900, or
greater than 90" (max 1200). With the gate in the desired position, mark a
second
point on the ground directly under the center of the gate bracket. Label
this point A2
(Figure 20).
|
|

|
 |
4. Determine where the operator output shaft
will be placed. With a string, connect
points Al and A2 and extend this line beyond A2. The operator shaft must be
on the
Al -A2 line, at least 12 inches away from the gate (Figure 2 1).
NOTE: Point C can be located anywhere on the A1-A2 line. However, the
farther away from the gate point C is made, the longer the operator
connecting arm will be.
5. Install the mounting plate / pipe assembly (or concrete base plate) in
accordance with
instructions detailed in this manual. Be sure that your mounting plate/ pipe
assembly,
or concrete base plate, and pad is located so that the operator output shaft
will intersect the Al -A2 line at the point that you have selected.
NOTE: Mount the plate / pipe assembly so that the operator will be square to
the fence line and not parallel to the gate when it is in the open position.
1.6.2 ARM LENGTH CALCULATIONS
After the operator has been installed, use the following steps to determine
the correct crank arm and connecting arm lengths for the installation.
1 . Measure the distance from point Al to point A2. Divide this measurement
by 2. The result is the length of the crank arm assembly from the operator
output shaft to the pivot point on the connector assembly.
2. Measure the distance from point Al to the operator output shaft. Subtract
from this measurement the length of the crank arm assembly that was
determined in step 1. The result is the length of the connecting arm.
|
|

|
SECTION 2 - WIRING
Before attempting to connect any wiring to the operator, be sure that the
circuit breaker in the electrical panel is in the OFF position. Permanent
wiring must be installed to the operator as required by local electrical
codes. It is recommended that a licensed electrical contractor perform this
work.
Since building codes vary from city to city, we highly recommend that you
check with your local building department prior to installing any permanent
wiring to be sure that all wiring to the operator (both high and low
voltage) complies with local code requirements.
THIS GATE OPERATOR MUST BE PROPERLY GROUNDED!!
|
 |
The conduit requirements shown in figure 22 are
for a typical swing gate operator installation (the slave operator is shown
for those applications where a slave operator may be used). The conduit
requirements for your application may vary from this depending on your
specific needs.
• Use only sweeps for conduit bends. Do not use 900 connectors as this will
make wire pulls very difficult and can cause damage to wire insulation.
• We suggest that minimum 3/4-inch conduit be used.
• Be sure that all conduits are installed in accordance with local codes.
|
|

|
2.1 HIGH VOLTAGE
CONNECTIONS
Use Table 4 to determine high voltage wire size requirements. The distance
shown in the chart is measured in feet from the operator to the power
source. If power wiring is greater than the maximum distance shown, it is
recommended that a service feeder be installed. When large gauge wire is
used, a separate junction box must be installed for the operator connection.
The wire table is based on stranded copper wire. Wire run calculations are
based on a 110 VAC power source with a 3% voltage drop on the power line,
plus an additional 10% reduction in distance to allow for other losses in
the system.
|
|
MODEL |
AMPS |
WIRE SIZE / DISTANCE IN FEET |
| 12 AWG |
10 AWG |
8 AWG |
6 AWG |
| 6050 SINGLE |
4.3 |
215 |
345 |
575 |
890 |
| 6050 M/S |
8.6 |
105 |
170 |
285 |
430 |
| 6100 SINGLE |
5.4 |
170 |
275 |
460 |
685 |
| 6100 M/S |
10.8 |
85 |
135 |
230 |
340 |
|
2.1.1 SINGLE OPERATOR
• Route incoming high voltage power through conduit and into the operator as
shown in Figure 23.
• Be sure wining is installed in accordance with local codes. Be sure to
color code all wiring.
• Connect BLACK power wire to the HOT terminal as shown.
• Connect WHITE neutral wire to NEUT terminal as shown.
• Connect GREEN ground wire to ground lug.
• It is recommended that a surge suppressor be installed on the high voltage
power lines to help protect the operator and circuit board from surges and
power fluctuations.
|
 |
|

|
2.1.2 MASTER / SLAVE OPERATORS
1. Connect the high voltage power lines to the MASTER operator as described
in 2.1.1
on the previous page. The master operator is the operator that has the
circuit board
installed in it. The slave operator does not have a circuit board.
2. The interface wiring between the two operators requires four (4) 16 AWG
wires for
motor power and grounding, and three (3) 18 AWG wires for low voltage
control.
Suggested wire colors for the high voltage lines are BLUE, RED and WHITE
(all 16
AWG), for the low voltage control lines YELLOW, BROWN and ORANGE (all 18
AWG). The ground wire should be GREEN (16 AWG). In the slave operator, place
a
jumper wire from terminal 19 to terminal 20. Note: DoorKing's master/slave
wire
cable (P/N 2600-75X) contains all of the above wires.
3. Connect BLUE and RED 16 AWG wires to the slave motor power terminal strip
(located at the top center of the 4502 circuit board in the master
operator). Connect
the other ends of these wires to terminals 4 and 5 in the slave operator. It
does not
matter which wire connects to which terminal.
4. Connect the WHITE 16 AWG wire from terminal 2 in the master operator to
terminal 2 in the slave operator.
5. Connect the GREEN 16 AWG wire to the ground lug in the master operator
and to
the ground lug in the slave operator.
6. Connect the YELLOW 18 AWG wire from terminal 8 in the master operator to
terminal 8 in the slave operator.
7. Connect the BROWN 18 AWG wire from terminal 10 in the master operator to
terminal 9 in the slave operator.
8. Connect the ORANGE 18 AWG wire from terminal 19 in the master operator to
terminal 19 in the slave operator.
|
 |
|

|
2.2 CONTROL WIRING
Controls must be far enough from the gate so that the user is prevented from
coming in contact with the gate while operating the controls. Outdoor or
easily accessible controls should have a security feature to prevent
unauthorized use.
• Connect optional control devices to the master operator terminal strip as
shown in Figure 25. Be sure that all electrical connections are made in
accordance with local electrical codes. Use 18 AWG wire for all low voltage
wiring, maximum distance 3000 feet. Use a low voltage surge suppressor,
DoorKing P/N 1878-010 if low voltage wire runs exceed 1000 feet. All inputs
to the terminal strip must be NORMALLY OPEN.
• Standard reversing input (term 15) only functions while the gate is in the
closing cycle and should not be used as an input for a secondary entrapment
protection device for the open gate cycle. See section 2.2.2 for secondary
entrapment protection device wiring.
• Do not power any devices from the circuit board other than a low voltage
radio receiver as shown in 2.2.1.
• Three-button control station must be DoorKing P/N 1200-006 only. Others
will not work.
• If magnetic lock is used, refer to section 2.4.
|
 |
|

|
2.2.1 RADIO RECEIVER WIRING
Connect the radio receiver to the master operator as shown in Figure 26. If
operators with battery backup are being used, refer to the supplemental
manual (p/n 2340-065) for radio receiver wiring options.
Power available at terminal 7 is limited to 250ma at 24 VAC. Do not power
any other device from this terminal.
If other control devices are used, they must be powered with their own power
supply.
|
 |
2.2.2 SECONDARY ENTRAPMENT PROTECTION DEVICE WIRING
This swing gate operator uses an inherent entrapment sensing system (Type A)
as the secondary entrapment protection device. Additional external
entrapment protection may be added to insure a safe vehicular gate operating
system. Additional inputs are available for non-contact sensors. Secondary
entrapment protection may be provided by a combination of non-contact (Type
B1), contact (Type B2) and inherent adjustable clutch (Type C) devices. See
Section 5.3 for a list of acceptable secondary entrapment protection
devices.
• Disconnect power to the gate operator before installing the non-contact
sensors.
• See Figure 27 for suggested placement of sensors. (Diagram is for
illustration purposes only. Actual placement of sensors is dependent on the
installation requirements).
• One or more non-contact sensors should be located where the risk of
entrapment or obstruction exist such as the perimeter reachable by a moving
gate or barrier.
• Use only U.L. listed (or equivalent) non-contact sensors.
• Connect the non-contact sensors as shown below. Inputs from the photo-beam
to the circuit board are Normally Open (N.O.). Diagram does not illustrate
power wiring to the photobeams. Refer to the photo-beam wiring diagram and
installation instructions for proper connection of photo-beam power.
• Photo-beam input to MAIN TERMINALS 15 and 20 will REVERSE travel of gate
when activated during the CLOSE CYCLE ONLY.
• Photo-beam input to AUXILIARY TERMINALS 7 and 8 will STOP gate travel in
either the OPENING or CLOSING cycle. Gate will resume normal operation when
photo-beam is no longer activated.
|
 |
|

|
2.3 LOOP DETECTOR WIRING
Loop detector wiring is shown for DoorKing model 9405 and 9406 Plug-in loop
detectors only. If other loop detectors are used, refer to the installation
instructions supplied with those detectors for wiring requirements.
If other loop detectors are used, all inputs to the terminal strip are
NORMALLY OPEN. Use a separate power supply to power external detectors. Be
sure that power is turned off prior to making any connections to the
terminal strip.
Loop layout shown is for a typical swing gate application with two-way
traffic or one-way exit only traffic. For one-way entry only traffic, the
open loop is replaced with a second reverse loop wired in series with the
first reverse loop. The 9506 detector is not needed in this application.
Refer to the separate Loop Information Manual (available from DoorKing) for
instructions on installing loops or preformed loops.
For correct SHADOW LOOP operation, jumper wire must be placed from terminal
15 to terminal 16, and SW I, switches 1 and 2 must be OFF. If a magnetic
lock is used, set switch 1 ON and switch 2 OFF.
NOTE: Output of Shadow Loop Detector may be connected directly to terminal
15 (doffed line - no jumper required between 15 and 16) if SW 2, switch 5 is
ON. However, with this switch ON, terminal 15 becomes a shadow input (active
only when the gate is FULL OPEN) and all reversing devices connected to
terminal 15 will operate as shadow devices. If this is not desirable, wire
the shadow loop detector as instructed in the above bullet point.
|
 |
|

|
2.4.1 DIRECT POWER
• Connect the magnetic lock as shown in Figure 29.
• 24-volt magnetic lock is connected directly to terminals 16 and 19 on the
4502 circuit board. Place a jumper wire from terminal 17 to terminal 18.
24-volt magnetic lock power is provided at terminals 18 and 19.
• Set relay contact shorting pin to NC (normally closed) operation (see
3.1).
• SW1, switch 1 must be in the ON position and SW1, switch 2 must be in the
OFF position when connecting a magnetic lock in this manner.
|
 |
2.4 MAGNETIC LOCK WIRING
2.4.2 INDIRECT POWER
• Connect the magnetic lock as shown in Figure 30.
• Requires the use of a DC transformer for magnetic lock power.
• Relay shorting pin on the 4502 circuit board must be set for NC (Normally
Closed) operation (see 3.1).
• SW1, switches I and 2 can be set in three different ways:
1 Switch 1 OFF, Switch 2 ON
2. Switch 1 ON, Switch 2 OFF
3. Switch I ON, Switch 2 ON
|
 |
|

|
2.5 GATE TRACKER CONNECTIONS
This gate operator is equipped with outputs from the circuit board that will
report operator status to a companion DoorKing Access Control System (Model
1803PC, 1815, 1817 or 1818) when equipped with an optional Tracker expansion
board. This report includes items such as gate operator cycle count, any
shorted inputs, loop detector problems, any attempts to force the gate open,
if the gate has struck anything during the open or close cycle, power
interruptions, etc.
Gate Tracker connections are made at the auxiliary terminal strip located at
the bottom of the circuit board, and at terminals 7, 11 and 20 on the main
terminal strip. For more detailed information on Gate Tracker and wiring to
the Tracker expansion boards, refer to the Tracker Installation and Wiring
Manual, DoorKing P/N 2351 -010.
Maximum wire run for gate operator data to the tracker board is 500 feet
using Belden #9931 shielded cable or Consolidated #5324-CL shielded cable.
Float the shield at the tracker board. Do not connect the shield to the
tracker board common.
Wire connection from the tracker board terminal P1 -5 to the 4502 main
terminal 11 is optional if the gate operator is not to be activated by the
tracker output relay.
|
 |
|

|
2.6 AUXILIARY DEVICES
2.6.1 ALARM RESET SWITCH
The gate operator is equipped with a reset switch that will silence the
entrapment alarm and return the operator to normal operation after a hard
shutdown occurs. An auxiliary reset button may be added provided that the
following condition is met.
• The alarm-reset button must be located in the line of sight of the gate.
• Connect the normally open alarm-reset switch to auxiliary terminals 2 and
3.
|
 |
2.6.2 AUXILIARY STOP SWITCH
This circuit creates an auxiliary stop input that will stop a moving gate
when activated, or will prevent the gate operator from starting if the
switch is activated. Note that this stop input is normally open and that a
switch closure will activate the stop function.
• This circuit cannot be used if a DoorKing 3 button control station is
connected to the operator.
• Place a jumper wire from terminal 13 to terminal 14.
• Connect the stop switch to terminals 14 and 20.
|
 |
|

|
2.7 MAIN TERMINAL DESCRIPTION
1. 115 VAC Neutral
2. 115 VAC Neutral Output To Slave Operator
3. 115 VAC Power Input
4. 115 VAC Motor Power (Open)
5. 115 VAC Motor Power (Close)
6. Not used
7. 24 VAC Radio Receiver Power Only (250 ma. maximum)
8. 12 VAC Magnetic Counter Power Only (150 ma. maximum)
9. PULSE 1 Input From Master Operator
10. PULSE 2 Input From Slave Operator
11. SINGLE BUTTON ACTIVATION INPUT 1
When gate is closed, input will open gate.
When gate is open and auto close timer is turned on, input will re-set and
hold timer.
When gate is open and auto close timer is turned off, input will close gate.
When gate is closing, input will reverse gate.
12. SINGLE BUTTON ACTIVATION INPUT 2 /OPEN LOOP LOGIC OUTPUT
If SW 1,switch 3 is ON, this input is identical to Single Button Activation
Input 1.
If SW 1, switch 3 is OFF, this terminal becomes the logic output of the OPEN
loop
detector.
13. OPEN INPUT - Use with DoorKing 3 button control station only (P/N
1200-006).
14. CLOSE INPUT - Use with DoorKing 3 button control station only (P/N
1200-006).
15. REVERSE (SAFETY) INPUT / SHADOW INPUT
When gate is closed, this input has no affect on the gate operator.
When gate is open and auto close timer is turned ON, input will re-set and
hold timer.
When gate is open and auto close timer is turned OFF, input will prevent
gate from
closing.
When gate is closing, input will reverse gate if SW 2, switch 5 is OFF.
When gate is closing, input has no affect on the gate operator if SW 2,
switch 5 is
ON.
16. DRY RELAY CONTACT
Operation of relay is dependent on setting of SW 1, switches 1 and 2. Relay
contacts
can be set for Normally Open (NO) or Normally Closed (NC) operation. Contact
rating is 1 amp maximum at 24 Volts.
17. DRY RELAY CONTACT
18. MAGNETIC LOCK OUTPUT
With SW 1, switch 1 ON and switch 2 OFF, 24-volt magnetic lock power is
provided
constantly except when the gate is opening or open.
19. LOW VOLTAGE COMMON
20. LOW VOLTAGE COMMON
|
|

|
2.8 AUXILIARY TERMINAL DESCRIPTION
The auxiliary terminal is located on the 4502 circuit board just to the
right of main terminals 18 and 19. Auxiliary terminals are numbered 1,
through 8.
1 . ALARM OUTPUT
Provides power to activate the entrapment alarm.
2. ALARM RESET INPUT
Input to reset the operator after an entrapment alarm.
3. COMMON
Common for alarm output and alarm reset input.
4. TRACKER DATA
Supplies gate operator data to Tracker expansion board (P/N 2351-010). Refer
to
the Tracker Installation and Wiring Manual for detailed information.
5. TRACKER DATA
Supplies gate operator data to Tracker expansion board (P/N 2351-010). Refer
to
the Tracker Installation and Wiring Manual for detailed information.
6. TRACKER DATA
Supplies gate operator data to Tracker expansion board (P/N 2351-010). Refer
to
the Tracker Installation and Wiring Manual for detailed information.
7. PHOTO-BEAM INPUT
This input will cause the gate operator to stop when activated in either the
opening or
closing cycles. The gate operator will remain stopped until the photo-beam
input is
cleared, at which time the operator will resume normal operation.
8. COMMON
Common for photo-beam input.
|
 |
|

|
SECTION 3 - ADJUSTMENTS
The switch settings and adjustments in this chapter should be made after
your installation and wiring to the operator(s) is complete. Whenever any of
the programming switches on the circuit board are changed, power must be
shut-off, and then turned back on for the new setting to take effect.
3.1 CIRCUIT BOARD ADJUSTMENTS
Set the DIP-switches on the circuit board to the desired setting. See
switch-setting charts in section 3.2.
Auto close timer (when turned on) can be set from 1 second (full counter
clockwise) to approximately 23 seconds (full clockwise).
Dry contact relay contacts (terminals 16-17) can be set for Normally Open
(NO) or Normally Closed (NC) operation by placing the relay shorting bar on
the NO or NC pins respectively.
Power LED indicates that low voltage power is applied to the circuit board.
Input LEDs should be OFF and will only illuminate when an input is
activated. The pulse LEDs will blink as the operator is running. They can be
either ON or OFF when the operator is stopped. Tracker LEDs will flash as
operator data is sent to the access controller (I 803PC, 1815, 1817 or
1818).
|
 |
|
|
|

|
3.2 SWITCH SETTINGS
The two DIP-switches located on the circuit board are used to program the
operator to operate in various modes and to turn on or off various operating
features. Whenever a switch setting is changed, power to the operator must
be turned OFF and then turned back on for the new setting to take affect.
Check and review ALL switch settings prior to applying power to the
operator.
|
|
SW I (TOP SWITCH) |
|
SWITCH |
FUNCTION |
SETTING |
DESCRIPTION |
|
1 and 2 |
Relay and |
1 -OFF |
2-OFF |
Relay activated only when gate is FULL OPEN. |
| |
Lock Power |
1-OFF |
2-ON |
Relay activated whenever gate is NOT CLOSED. |
| |
|
1-ON |
2-OFF |
Relay activated, magnetic lock power OFF when gate is OPENING and OPEN. |
| |
|
1-ON |
2-ON |
Relay activated when gate is OPENING and CLOSING. |
|
3 |
Open Loop |
OFF |
|
Output of loop detector in OPEN port is switched to terminal 12. |
| |
Logic Output |
ON |
|
Output of loop detector in OPEN port feeds directly to processor. |
|
4 |
Auto-Close |
OFF |
|
Auto-close timer is OFF. Manual input required to close gate. |
| |
Timer |
ON |
|
Auto=close timer is ON. Adjustable from 1-23 seconds. |
|
5 |
Slide Gate |
OFF |
|
Switch is in the OFF position for slide gate operators. |
| |
Swing Gate |
ON |
|
Switch is in the ON position for swing gate operators. |
|
6 |
3-Button Control |
OFF |
|
Switch must be OFF when 3-button control is used. |
| |
|
ON |
|
Switch must be ON when single button control is in use. |
|
7 |
Bi-parting Gates |
OFF |
|
Switch is OFF when bi-parting (master-slave) gates are used. |
|
|
Single Gate |
ON |
|
Switch is ON for single gate operation. |
|
8 |
Tamper Protect |
OFF |
|
Tamper protect is turned OFF. |
|
|
|
ON |
|
Tamper protect is turned ON. |
|
|
SW 2 (BOTTOM SWITCH) |
|
SWITCH |
FUNCTION |
SETTING |
DESCRIPTION |
|
1 |
Direction |
OFF |
Changes direction of MASTER operator. Set so that the operator |
| |
Master |
ON |
runs in the OPEN direction upon initial activation after power-up. |
|
2 |
Direction |
OFF |
Changes direction of SLAVE operator. Set so that the operator |
| |
Slave |
ON |
runs in the OPEN direction upon initial activation after power-up. |
|
3 |
Self Test |
OFF |
Normal operation. |
| |
|
ON |
Self test. Operator must be disconnected from gate to run test. |
|
4 |
Motor Control |
OFF |
Switch is OFF when both master and slave operator motors are powered
from main terminals 4 and 5. Applies to operators originally
manufactured with 4501, Rev 0 boards or lower). |
| |
|
ON |
Switch is ON when slave operator motor is powered from the slave motor
terminals. Applies to operators manufactured with 4501, Rev P boards and
higher. |
|
5 |
Shadow Input |
OFF |
Terminal 15 is a standard REVERSE input with this switch OFF. |
| |
|
|