835/836 UL Operator Control Board

835/836 Control Board Parts Identification

| |
ACTUATOR CONNECTOR |
 |
| Board |
Actuator Cable |
Function |
| Pin 1 |
Orange |
Open Limit |
| Pin 2 |
White |
Close Limit |
| Pin 3 |
Black |
Motor (positive on open, negative on
close) |
| Pin 4 |
Red |
Motor (negative on open, positive on
close) |
| Pin 5 |
Green |
Common for both limit switches |
| Pin 6 |
Yellow |
Feedback from intelligent actuator
(816E/816EX) |
| Pin 7 |
Black |
Battery Negative |
| Pin 8 |
Red |
Battery Positive |
|
| |
EMERGENCY BYPASS |
 |
Applies battery voltage directly to motor to open gate if
control board fails. User must unplug before
gate opens to maximum travel or 15 amp fuse will open. Fuse should be
checked before returning gate to service.
|
| |
REMOTE OUTPUTS |
 |
12V Supplied battery voltage
SLV Slave Operator Indicator (indicates slave side of gate is closed)
+1 2V when on closed limit. Ground when off of closed limit.
MAS Master Operator Indicator (indicates master side of gate is
closed)
+1 2V when on closed limit. Ground when off of closed limit
SND Battery supplied ground
SIREN Conned to siren + (optional)
+1 2V when gates) are running or in hard shutdown
SND Battery supplied ground
LOCK Connect to lock + (optional) Magnetic or Solenoid type locks
(Dip Switch #6 Selectable) |
| |
GATELINK CONNECTOR |
 |
Connects control board to a computer using GateLink
software. This software can monitor and diagnose the
functions of the microprocessor. Ask your salesperson about this feature. |
| |
ADJUSTMENTS |
 |
TIMER TO CLOSE Adjusts time before gate automatically
closes 1-60 seconds,
DUAL GATE DELAY (836 only) Adjusts delay between master and save
operation 0-4 seconds. (for use with magnetic and mechanical locks or
stop tabs)
CURRENT SENSITIVITY Increases or decreases the Auto Reverse
sensitivity |
| |
PUSH BUTTONS |
 |
LED ENABLE When depressed, activates LEDs for 15
minutes to assist in installation and
troubleshooting. |
 |
RESET Resets the microprocessor. Returns processor to
last known state. |
| |
JUMPERS |
 |
STOP CIRCUIT JUMPER When the STOP CIRCUIT JUMPER
is connected, the gate will operate normally. |
 |
STOP CIRCUIT JUMPER When a 3-button station is
connected to the
board, the STOP CIRCUIT JUMPER must be
removed. |
PROGRAM SWITCHES

| |
OFF |
ON |
| 1 TIMER TO CLOSE |
Gate does not automatically close. |
Gate automatically closes |
| 2 TIMER TO CLOSE OPT. |
Gate automatically closes from any position after opening. |
Gate automatically closes only when completely open (open
limit engaged) |
| 3 SLAVE DISABLE |
Enables slave side (dual gate use). |
Disables slave side. (single gate use) |
| 4 SIREN DELAY |
Siren (optional) starts when gate moves |
Siren (optional) starts 3 seconds before gate moves. |
| 5 'STOP' CIRCUIT ENABLE |
Must hold down open or close buttons to move gate. Gate
stops when button released. |
Normal operation Momentary open or close runs gate to limit. |
| 6 LOCK TYPE |
For 12V mechanical (solenoid) locks. (+12V for 4 seconds an
open cycle) |
For 12V magnetic looks (+12V when on close limit) |
| 7 COAST ENABLE |
Gate will brake when at Open or Close limit |
Gate will coast (minimally) when it reaches limits. |
| 8 FREE EXIT OPT. |
A free exit input will open gate from closed position or
after a close cycle only. |
A free exit input will open gate from any position after an
open or close cycle |
| 9 LEARN MODE |
Normal Operation |
Control board determines reverse current sensitivity and
when to start slowing down opening and closing (used during installation), |
| 10 SMART ACT. |
Used for 416E & 416EX actuators, slide gates, or when slow
down feature is not desired |
Used for 816E & 816EX actuators (soft start & stop). |
OPTIONAL DEVICE INPUTS
 |
GND Supplied Battery Ground
INP Activate Gate (Push button activation when momentarily shorted to
ground)
12V Supplied Battery Voltage (Protectecf with 3 Amp fuse) |
 |
GND Supplied Battery Ground
INP Activate Gate (Push button activation when momentarily shorted to
ground)
12V Supplied Battery Voltage (Protected with 3 Amp fuse) |
 |
EDGE Reverse edge input. When grounded, will stop and
reverse gate if closing, resets close timer if gate is open.
EDGE Reverse edge input. When grounded, will stop and reverse gate If
closing resets close timer if gate is open
GND Supplied Battery Ground
GND Supplied Battery Ground
STOP Stop input from a 3 button station (must remove STOP CIRCUIT
JUMPER) Normally closed
CLOSE Close input from a 3 button station (see program switch #5 for
options)
OPEN Open input from a 3 button station (see program switch #5 for
options) |
 |
GND Supplied Battery Ground
GND Supplied Battery Ground
FREE EXIT Opens gate if closed, stops and reverses gate if closing,
resets close timer if gate is open
GND Supplied Battery Ground
SHADOW Resets close timer when gate is open (also referred to as
under gate loop)
GND Supplied Battery Ground
SAFETY Resets close timer if gate is open, stops and reverses if gate
is closing. (Does not open a closed
gate) |
 |
GND Supplied Battery Ground
FIRE When grounded, opens gate and holds gate open until released.
UL When grounded, opens gate and holds gate open until released.
Clears 'Hard Shutdown" mode of UL software. |
 |
GND Supplied Battery Ground
INP Activate Gate (Push button activation when momentarily shorted to
ground)
12V Supplied Battery Voltage (Protected with 3 Amp fuse) |
911 Siren
The 911 Siren is included with all Apollo UL Gate Operators.
Mount siren in an area that will produce maximum performance (additional wire
may be required).
Connect the red wire to the SIREN connector on the Remote Monitor Output
Connector block.
Connect the black wire to the GND connector on the Remote Monitor Output
Connector block.

Set Program Switch # 4 as preferred:
ON - Upon activation, Siren will start for 5 seconds before gate(s) begin
moving.
OFF - Siren and gate(s) start immediately upon activation.
|